Operation frequency

6.6.1
Starting frequency
• Function
The frequency set with the parameter
ting.
Use the
tion/deceleration time is probably affecting operation. Setting the starting frequency to a value from 0.5
to 2Hz (maximum: 5Hz) is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title
Starting frequency setting
Starting frequency setting
: Starting frequency setting
parameter when a delay in response of starting torque according to the accelera-
Function
Output frequency [Hz]
F-17
is put out immediately on completion of frequency set-
Adjustment range
0.5 ∼ 10.0 (Hz)
E6580757
Default setting
0.5
6
Time [sec]