Avoiding Overvoltage Tripping; Overvoltage Limit Operation - Toshiba TOSVERT VF-S9 Instruction Manual

Compact inverter 1-phase 200v class 0.2 2.2kw 3-phase 200v class 0.2 15kw 3-phase 400v class 0.75 15kw
Hide thumbs Also See for TOSVERT VF-S9:
Table of Contents

Advertisement

4) Minimum resistances of connectable braking resistors
The minimum allowable resistance values of the externally connectable braking resistors are listed in the ta-
ble below.
Do not connect braking resistors with smaller resultant resistances than the listed minimum allowable resis-
tance values.
Inverter rated
output capacity

6.12.5 Avoiding overvoltage tripping

6
• Function
Output
frequency
DC voltage
[Parameter setting]
Title
Resistance of
(kW)
standard option
0.2
200Ω
0.4
200Ω
0.75
200Ω
1.5
75Ω
2.2
75Ω
3.7
40Ω
5.5
20Ω
7.5
15Ω
11
10Ω
15
7.5Ω

: Overvoltage limit operation

This parameter keeps the output frequency constant or increases the frequency to prevent overvolt-
age tripping due to increases in DC voltage during deceleration or constant-speed operation. The
deceleration time during overvoltage limit operation may increase above the designated time.
Overvoltage limiting level
Function
Overvoltage limit operation
200V class
Minimum allowable
resistance
63Ω
63Ω
42Ω
30Ω
30Ω
24Ω
10Ω
10Ω
7Ω
7Ω
Overvoltage limiting level
Adjustment range
0: Enabled
1: Prohibited
F-30
E6580757
400V class
Resistance of
Minimum allowable
standard option
resistance
-
-
-
-
200Ω
99Ω
200Ω
99Ω
200Ω
73Ω
160Ω
73Ω
80Ω
44Ω
60Ω
44Ω
40Ω
22Ω
30Ω
22Ω
Default setting
0