6. Extended parameters

Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. Modify pa-
rameter settings as required. See Section 11, Table of extended parameters.
6.1

Input/output parameters

6.1.1
Low-speed signal
• Function
When the output frequency exceeds the setting of this parameter, an ON signal will be generated. This
signal can be used as an electromagnetic brake excitation/release signal.
Relay output (250Vac-2A (cos φ = 1), 30Vdc-1A, 250Vac -1A (cos φ = 0.4) at RY-RC or FLA-FLC-
FLB terminals (Default setting: RY-RC).
Open-collector output (24Vdc-50mA [maximum]) can also be set at OUT terminal.
[Parameter setting]
Title
: Low-speed signal output frequency
Function
Low-speed signal output frequency
Output frequency
[Hz]
Set frequency
Low-speed signal output
RY-RC terminals (Default setting)
P24-OUT terminals
FLA-FLC-FLB terminals
Low-speed signal output: Inverted
F-1
Adjustment range
0.0 ∼
(Hz)
Time [sec]
E6580757
6
Default setting
0.0