Freeze Prevention - Daikin FCQ18PVJU Service Manual

Split system air conditioners skyair inverter r-410a heat pump 60hz p series
Hide thumbs Also See for FCQ18PVJU:
Table of Contents

Advertisement

Other Control
5.5

Freeze Prevention

Freeze
When the temperature detected by the liquid pipe temperature thermistor (R2T) of the indoor
unit heat exchanger drops too low, the unit enters freeze prevention operation in accordance
Prevention by Off
with the following conditions, and is also set in accordance with the conditions given below.
Cycle (Indoor
Unit)
Conditions for starting freeze prevention: Temperature is 30°F or less for total of 40 min., or
temperature is 23°F or less for total of 10 min.
Conditions for stopping freeze prevention: Temperature is 45°F or more for 10 min.
continuously.
Ex: Case where temperature is 23°F or less for total of 10 min.
39
SiUS28-902_a
Function