Field Setting
b. "Setting mode 2"
Push and hold the MODE button
(BS1) for 5 seconds and set to
"Setting mode 2".
<Selection of setting items>
Push the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
¯
Push the RETURN button (BS3) and
decide on the item. (The present
setting condition is blinking.)
<Selection of setting conditions>
Push the SET button (BS2) and set
to the setting condition you want.
¯
Push the RETURN button (BS3) and
decide the condition.
Push the RETURN button (BS3) and
set to the initial status of "Setting
mode 2".
* If you become unsure of how to
proceed, push the MODE button
(BS1) and return to setting mode 1.
57
No.
Setting item
Indoor unit forced
Allows forced operation of indoor unit fan while unit is
5
fan H
stopped. (H tap)
Indoor unit forced
6
Allows forced operation of indoor unit.
operation
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10 Defrost changeover
Changes the temperature condition for defrost and sets to
setting
quick defrost or slow defrost.
External low noise
12
setting / Demand
Reception of external low noise or demand signal
setting
Refrigerant
recovery /
21
Sets to refrigerant recovery / vacuuming mode.
vacuuming mode
setting
Sets automatic nighttime low noise operation in a simple
22 Night-time low
way.
noise setting
The operating time is based on "Starting set" and "Ending
set".
Night-time low
Sets starting time of nighttime low noise operation.
26
noise operation
(Night-time low noise setting is also required.)
start setting
Night-time low
Sets ending time of nighttime low noise operation.
27
noise operation
(Night-time low noise setting is also required.)
end setting
If the capacity control is required, the low noise control is
Capacity
29
automatically activated by this setting.
precedence setting
Changes target value of power consumption when
30 Demand setting 1
demand control 1 is input.
Normally enables demand control 1 without external
32 Normal demand
input. Effective to prevent a problem that circuit breaker
setting
of of small capacity is shut down due to large load.
SiUS28-902_a