Daikin FCQ18PVJU Service Manual page 149

Split system air conditioners skyair inverter r-410a heat pump 60hz p series
Hide thumbs Also See for FCQ18PVJU:
Table of Contents

Advertisement

SiUS28-902_a
Troubleshooting
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
the connector, or parts could be damaged.
Is
electricity
being introduce for
YES
the first time after
installation after an indoor
or outdoor unit P.C.B.
has been
replaced?
NO
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
YES
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit
P.C.B. for 5 seconds
Does a malfunction
occur?
YES
Does
UH
a "
" malfunction occur
for all indoor units in
the system?
YES
Troubleshooting by Indication on the Remote Controller
Does
a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor
and outdoor
units?
YES
NO
NO
NO
NO
Normal
After fixing incorrect wiring,
push and hold the RESET
button on the master outdoor
unit P.C.B. for 5 seconds.
* The unit will not run for up to
12 minutes.
Normal
Replace the indoor unit P.C.B.
Replace the outdoor unit
P.C.B. (A1P).
142