L8" Outdoor Unit: Inverter Current Abnormal - Daikin FCQ18PVJU Service Manual

Split system air conditioners skyair inverter r-410a heat pump 60hz p series
Hide thumbs Also See for FCQ18PVJU:
Table of Contents

Advertisement

SiUS28-902_a
L8
3.31 "
" Outdoor Unit: Inverter Current Abnormal
L8
Remote
Controller
Display
Applicable
RZQ18~30PVJU
Models
Method of
Malfunction is detected by current flowing in the power transistor.
Malfunction
Detection
Malfunction
When overload in the compressor is detected.
Decision
Conditions
 Compressor overload
Supposed
 Compressor coil disconnected
Causes
 Defect of outdoor unit P.C.B. (A1P)
Troubleshooting