SiUS28-902_a
L8
3.31 "
" Outdoor Unit: Inverter Current Abnormal
L8
Remote
Controller
Display
Applicable
RZQ18~30PVJU
Models
Method of
Malfunction is detected by current flowing in the power transistor.
Malfunction
Detection
Malfunction
When overload in the compressor is detected.
Decision
Conditions
Compressor overload
Supposed
Compressor coil disconnected
Causes
Defect of outdoor unit P.C.B. (A1P)
Troubleshooting
Troubleshooting by Indication on the Remote Controller
124