Fhq; Ceiling Suspended Type - Daikin FCQ18PVJU Service Manual

Split system air conditioners skyair inverter r-410a heat pump 60hz p series
Hide thumbs Also See for FCQ18PVJU:
Table of Contents

Advertisement

SiUS28-902_a
1.2

FHQ

Ceiling Suspended Type

Indoor unit
Model
Outdoor unit
Power supply
Cooling capacity ¹
Heating capacity ²
Indoor unit
Color
Dimensions
H×W×D
Type
Coil
Rows×Stages×FPI
Face area
Model
Type
Fan
Motor output
Airflow rate (H/L)
Air filter
Mass (Weight)
Liquid
Piping
Gas
connections
Drain
Wired
Remote controller (option)
Wireless
Outdoor unit
Color
Dimensions
H×W×D
Type
Coil
Rows×Stages×FPI
Face area
Model
Comp.
Type
Motor output
Model
Type
Fan
Motor output
Airflow rate
Mass (Weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Standard length
Ref. piping
Max. length
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing Number
Notes:
1. The above data are based on the following conditions.
Cooling ∗1
Indoor : 80°FDB, 67°FWB
Indoor : 70°FDB
Outdoor : 95°FDB
Outdoor : 47°FDB, 43°FWB
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Specifications
FHQ18PVJU
RZQ18PVJU
1 phase 60Hz 208-230V
Btu/h
18,000
Btu/h
20,000
FHQ18PVJU
White (10Y9/0.5)
7–11/16 × 62–5/8 × 26–3/4
in (mm)
(195 x 1590 x 680)
Cross fin coil
2 × 12 × 15 + 2 × 10 × 15
ft²
3.66 + 2.95
Sirocco fan
W
130
cfm
790/670
Resin net (With mold resistant)
Lbs (kg)
90 (41)
φ3/8 (9.5) (Flare Connection)
in (mm)
φ5/8 (15.8) (Flare connection)
in (mm)
VP20 (External dia. 1 (25.4),
in (mm)
Internal dia. 3/4 (19.1)
BRC1D71
BRC7E83
RZQ18PVJU
Ivory
30–5/16 × 35–7/16 × 12–5/8
in (mm)
(770 x 900 x 320)
Cross fin coil
2 × 34 × 18
ft²
7.1
2YC63HXD#ED
Hermetically sealed swing type
kW
1.7
P47N11F
Propeller fan
W
70
cfm
1,835
Lbs (kg)
150 (68)
φ3/8 (9.5) (Flare connection)
in (mm)
φ5/8 (15.8) (Flare connection)
in (mm)
φ1 (25.4) (Hole)
in (mm)
High pressure switch.
Outdoor fan driver overload protector.
Thermal protector for indoor fan motor.
Inverter overload protector.
Fusible plugs. Fuse.
%
100-0
Electronic expansion valve
ft (m)
25 (7.5)
ft (m)
164' (50)
ft (m)
98' (30)
R410A
Lbs (kg)
5.1 (2.3)
Refer to the name plate of compressor.
L
0.75
C : 4D063925C
Heating ∗2
Equivalent Piping Length
25 ft (7.5 m) (Level Difference : 0)
FHQ24PVJU
RZQ24PVJU
1 phase 60Hz 208-230V
24,000
27,000
FHQ24PVJU
White (10Y9/0.5)
7–11/16 × 62–5/8 × 26–3/4
(195 x 1590 x 680)
Cross fin coil
2 × 12 × 15 + 2 × 10 × 15
3.66 + 2.95
Sirocco fan
130
790/670
Resin net (With mold resistant)
90 (41)
φ3/8 (9.5) (Flare connection)
φ5/8 (15.8) (Flare connection)
VP20 (External dia. 1" (25.4 mm),
Internal dia. 3/4" (19.1 mm)
BRC1D71
BRC7E83
RZQ24PVJU
Ivory
30–5/16 × 35–7/16 × 12–5/8
(770 x 900 x 320)
Cross fin coil
2 × 34 × 18
7.1
2YC63HXD#ED
Hermetically sealed swing type
1.7
P47N11F
Propeller fan
70
1,835
150 (68)
φ3/8 (9.5) (Flare connection)
φ5/8 (15.8) (Flare connection)
φ1 (25.4) (Hole)
High pressure switch.
Outdoor fan driver overload protector.
Thermal protector for indoor fan
motor.
Inverter overload protector.
Fusible plugs. Fuse.
100-0
Electronic expansion valve
25 (7.5)
164' (50)
98' (30)
R410A
5.1 (2.3)
Refer to the name plate of
compressor.
0.75
C : 4D063925C
Hz, Volts
60Hz, 230V
Specifications
FHQ30PVJU
RZQ30PVJU
1 phase 60Hz 208-230V
30,000
34,000
FHQ30PVJU
White (10Y9/0.5)
7–11/16 × 62–5/8 × 26–3/4
(195 x 1590 x 680)
Cross fin coil
2 × 12 × 15 + 2 × 10 × 15
3.66 + 2.95
Sirocco fan
130
790/670
Resin net (With mold resistant)
90 (41)
φ3/8 (9.5) (Flare connection)
φ5/8 (15.8) (Flare connection)
VP20 (External dia. 1" (25.4),
Internal dia. 3/4" (19.1)
BRC1D71
BRC7E83
RZQ30PVJU
Ivory
30–5/16 × 35–7/16 × 12–5/8
(770 x 900 x 320)
Cross fin coil
2 × 34 × 18
7.1
2YC63HXD#ED
Hermetically sealed swing type
1.7
P47N11F
Propeller fan
70
1,835
150 (68)
φ3/8 (9.5) (Flare connection)
φ5/8 (15.8) (Flare connection)
φ1 (25.4) (Hole)
High pressure switch.
Outdoor fan driver overload
protector.
Thermal protector for indoor fan
motor.
Inverter overload protector.
Fusible plugs. Fuse.
100-0
Electronic expansion valve
25 (7.5)
164' (50)
98' (30)
R410A
5.1 (2.3)
Refer to the name plate of
compressor.
0.75
C : 4D063925C
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents