Installation Manual
9-11 Perform a test run.
(1) Before turning on the power supply, be sure to check that
the control box cover is closed.
(2) Perform a test run according to "OPERATION MANUAL".
• An error code is displayed on the remote controller when
an malfunction occurs. Check the error code on the dis-
play to identify the point of trouble. An explanation of
error codes and the corresponding trouble is provided in
"OPERATION MANUAL".
If the display shows any of the following, there is a possi-
bility that the wiring was done incorrectly or that the
power supply is not ON, so check again.
Remote controller display Content
U8
No display
10. DESCRIPTION OF SYSTEM AND
APPLICABLE PATTERNS
10-1 INDEPENDENT SYSTEM
10-1-1 When connecting to remote controller
(Refer to "9. FIELD SETTING AND TEST RUN".)
Check the switch "SS1" on the PC board to the factory setting.
Factory Setting
Do not change the switch setting.
SS1 is a setting switch for special purposes.
Changing the setting will stop the unit from
operating normally.
1. Main remote controller
2. Sub remote controller
3. Maximum transmission wiring length : 1640 ft.
15
30
• Incorrect setting the MAIN/SUB of the
remote controller.
• The power supply to the unit is off.
• The indoor unit and/or ERV have not
been wired for power supply.
• Incorrect wiring for the remote control-
ler, the transmission wiring and / or
the FORCED OFF wiring.
• The remote controller wiring is discon-
nected.
• Incorrect setting the "SS1" switch of
PC board.
NOR
H
M
10-2 Interlocking system with VRV system
10-2-1 Standard 1-group linked operation system
• The remote control can be used to control up to 16 air condi-
tioner indoor units and ERV units.
• Initial settings can be made for the functions of the ERV
units (pre-cool/pre-heat, ventilation rate, ventilation mode
and "Fresh up").
Use the remote controller to make the initial settings for the
ERV units.
Refer to "9. FIELD SETTING AND TEST RUN".
1. Main remote controller
2. Sub remote controller
3. Transmission wiring can be extended up to 1640 ft.
Pre-cool/pre-heat function
When the pre-cool/pre-heat function is set, the ERV unit will be
turned on at the preset time (30, 45 or 60 minutes) after the
VRV-system air conditioner begins cooling or heating opera-
tion. The function is set OFF at the factory.
Therefore, to use this function, the initial setting must be made
using the remote controller.
If the air conditioner is re-started within two hours after the
operation stopped, this function is disabled.
Example 1:
To switch on the pre-cool/pre-heat function and turn on the
ERV unit 60 minutes after the air conditioner is turned on.
(1) Set the mode No. to "17" for group control or "27" for indi-
vidual control, the FIRST CODE NO. to "2" and the SEC-
OND CODE NO. to "02"
(2) Set the mode No. to "17" for group control or "27" for indi-
vidual control, the FIRST CODE NO. to "3" and the SEC-
OND CODE NO. to "03"
Example 2:
To switch the ventilation airflow to extra high setting.
(The units are set at the high airflow setting at the factory)
Set the mode No. to "17" for group control or "27" for individual
control, the FIRST CODE NO. to "4" and the SECOND CODE
NO. to "02"
EDUS711116
English
3P034928-7Q
VAM-GVJU