2-9. ELECTRICAL REQUIREMENTS
OFG-320 SERIES (Continued)
2-10. ELECTRICAL REQUIREMENTS
OFE-320 SERIES
DRYWALL CONSTRUCTION
Secure I-bolt to a building stud. Do
not attach to drywall only. Preferred
installation is approximately six
inches to either side of service.
Cable restraint must be at least six
inches shorter than flexible conduit.
2-7
To avoid electrical shock, do not disconnect the ground
(earth) plug. This fryer must be adequately and
safely grounded (earthed). Refer to local electrical
codes for correct grounding (earthing) procedures or in
absence of local codes, with The National Electrical
Code, ANSI/NFPA No. 70-(the current edition). In
Canada, all electrical connections are to be made in
accordance with CSA C22.1, Canadian Electrical Code
Part 1, and/or local codes.
Refer to the table below for supply wiring and fusing.
Volts
Phase
200-208
3
220/240
3
440-480
3
380-415
3
To avoid electrical shock, this appliance must be
equipped with an external circuit breaker which will
disconnect all ungrounded (unearthed) conductors.
The main power switch on this appliance does not
disconnect all line conductors.
To avoid electrical shock, this fryer must be
adequately and safely grounded (earthed). Refer to
local electrical codes for correct grounding (earthing)
procedures or in absence of local codes, with The
National Electrical Code, ANSI/NFPA No. 70-(the
current edition). In Canada, all electrical connections are
to be made in accordance with CSA C22.1, Canadian
Electrical Code Part 1, and/or local codes.
CE units require a minimum wire size of 6 mm to be wired
to the terminal block.
Permanently connected electric fryers with casters must be
installed with flexible conduit and a cable restraint, when
installed in the United States. See illustration at left. Holes
are available in the rear fryer frame for securing the cable
restraint to the fryer. The cable restraint does not prevent the
fryer from tipping.
Model OFE/OFG-321,322,323,324
(Per Well)
Kw
14.4
14.4
14.4
14.4
Amps
40
40
17
20
705