Maintenance

7-2
Maintenance
7-2-1
Cleaning
7-2-2
Inspection
Inspection Equipment
Equipment Required for
Regular Inspection
Other Equipment that May
Be Required
Inspection Procedure
Inspection item
Environmental conditions
Installation conditions
This section describes the routine cleaning and inspection recommended as
regular maintenance. Handling methods when replacing Controllers are also
explained here.
Clean the Controllers regularly as described below in order to keep the Net-
work in its optimal operating condition.
• Wipe the Controller with a dry, soft cloth for regular cleaning.
• When dust or dirt cannot be removed with a dry cloth, dampen the cloth
with a neutral cleanser (2%), wring out the cloth, and wipe the Controller.
• Smudges may remain on the Controller from gum, vinyl, or tape that was
left on for a long time. Remove these smudges when cleaning.
Note Never use volatile solvents, such as paint thinner or benzene, or chemical
wipes to clean the Controller. These substances may damage the surface of
the Controller.
Inspect the system periodically to keep it in its optimal operating condition.
In general, inspect the system once every 6 to 12 months, but inspect more
frequently if the system is used in high-temperature, humid, or dusty condi-
tions.
Prepare the following equipment before inspecting the system.
A flat-blade and a Phillips screwdriver, a screwdriver for connecting communi-
cations connectors, a tester (or a digital voltmeter), industrial alcohol, and a
clean cloth are required for routine inspection.
A synchroscope, oscilloscope, thermometer, or hygrometer may be required.
Check the items in the following table and correct any condition that is below
standard by adjusting the Controller or improving the environmental condi-
tions.
Details
Are ambient and cabinet temperatures
correct?
Are ambient and cabinet humidity cor-
rect?
Has dust or dirt accumulated?
Are the connectors of the communica-
tions cables fully inserted?
Are the external wiring screws tight?
Are the connecting cables undamaged?
Standard
°
10 to +55
C
Thermometer
25% to 85%
Hygrometer
No dust or dirt
Visual inspection
No looseness
Phillips screwdriver
No looseness
Phillips screwdriver
No external damage
Visual inspection