Attaching The Devicenet Communications Unit Connector - Omron E5ARER User Manual

Digital controller devicenet communications
Table of Contents

Advertisement

DeviceNet Communications Cables Wiring
3-3-2

Attaching the DeviceNet Communications Unit Connector

3-16
Blue (CAN low)
Black (−V)
The colors correspond to the signal lines as follows:
Color
Red
Power line, positive voltage (+V)
White
Communications line, high (CAN high)
---
Shield
Blue
Communications line, low (CAN low)
Black
Communications cable, negative voltage (−V)
• We recommend the following crimp terminals (for Thin Cables)
Power Lines: Phoenix Contact AI-series Crimp Terminals AI-0.5-6WH
(product code 3200687)
Signal Lines: Phoenix Contact AI-series Crimp Terminals AI-0.25-6BU
(product code 3201291)
Line
Crimp terminal
Insert the line and crimp.
The following crimp tool is also available.
Phoenix Contact ZA3 Crimp Tool
Align the DeviceNet Communications Unit connector with the cable connec-
tor, and insert the cable connector fully into the DeviceNet Communications
Unit connector.
Tighten the set screws to a torque between 0.25 and 0.3 N·m to secure the
connector.
E5AR
Red (+V)
White (CAN high)
Shield
Signal