Make Gas Connection - Jenn-Air W10526082A Installation Instructions Manual

30" (76.2 cm) gas downdraft slide-in ranges
Table of Contents

Advertisement

Available languages

Available languages

WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person make sure
gas pressure does not exceed 14" (36 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
Typical flexible connection
1. Open access panel by grasping sides and pulling upward,
lifting out.
2. Locate gas pressure regulator behind access panel.
A
A. Gas pressure regulator
3. Apply pipe-joint compound made for use with LP gas to the
smaller thread ends of the flexible connector adapters (see B
and G in the following illustration).
4. Attach one adapter to the gas pressure regulator and the
other adapter to the gas shutoff valve. Tighten both adapters.

Make Gas Connection

5. Use a
attach the flexible connector to the adapters. Check that
connector is not kinked.
A. Gas pressure regulator
B. Use pipe-joint compound.
C. Adapter (must have ½" male
pipe thread)
D. Flexible connector
6. Gas supply pipe must not be more than 10" (25.4 cm) above
the floor.
Complete Connection
1. Open the manual shutoff valve in the gas supply line. The
valve is open when the handle is parallel to the gas pipe.
2. Test all connections by brushing on an approved
noncorrosive leak-detection solution. If bubbles appear, a
leak is indicated. Correct any leak found.
3. Remove cooktop burner caps and grates from package
containing parts. Align recess in burner caps with pins in
burner base. Burner caps should be level when properly
positioned. If burner caps are not properly positioned,
surface burners will not light. Place burner grates over
burners and caps.
" combination wrench and an adjustable wrench to
A
B C
D
H
E. Manual gas shutoff valve
F. ½" or ¾" gas pipe
G. Use pipe-joint compound.
H. Adapter
A. Flexible connector
B. Manual shutoff valve
C. 10" (25.4 cm) max. straight pipe
A
A. Closed valve
B. Open valve
E
G
F
B
15