6.29.10 Canceling PID control in panel operation mode


Function
This parameter is to switch from PID control to open-loop control (normal control
mode) when PID control is exercised by the control panel.
Note) This parameter is valid only when the inverter is in panel operation mode.
 PID control enabled
PID control is exercised if  is not set at .
 PID control disabled
Open-loop control (normal control mode) is exercised instead of PID control.
[Parameter setting]
Title
Panel PID control OFF

Note) When  is set at , open-loop control is exercised even if this parameter is
set at  (PID control enabled).

6.29.11 Setting a torque command in panel operation mode


Function
This parameter is to set a torque command when torque control is exercised by the
operation panel. This parameter is valid only when the inverter is in control panel
operation mode.
Panel operation: Torque command selection
[Parameter setting]
Title
Panel torque reference

Refer to 3.3.3 for details.

6.29.12 Drooping control in panel operation mode





6.29.13 Override in panel operation mode


Refer to 6.27 for details.
Panel PID control OFF
Function
Panel torque reference
Function
Panel synchronized torque bias
Panel tension torque bias
Panel load sharing gain
Panel over-ride multiplication gain
F-70
Adjustment range
: ON
: OFF
is set at (Panel input).

Adjustment range
  [%]
Default setting
Default setting