4=3. TEST RUN
• Be sure to perform the test run for each unit. Make sure each indoor unit operates properly following the installation manual attached to the unit.
• If you perform the test run for all indoor units at once, you cannot detect any erroneous connection,
if any, of the refrigerant
pipes and the indoor/outdoor
unit connecting
wires.
About
the restart
protective
mechanism
Once the compressor
stops, the restart preventive
device operates so the compressor
will not operate for 3 minutes to protect the air conditioner.
4=4. EXPLANATION
TO THE USER
• Using the OPERATING
INSTRUCTIONS,
explain to the user how to use the air conditioner
(how to use the remote controller,
how to remove the air fil-
ters, how to remove or put the remote controller
in the remote controller
holder, how to clean, precautions
for operation,
etc.)
• Recommend
the user to read the OPERATING
INSTRUCTIONS
carefully.
5=1. PUMPING DOWN
When relocating or disposing
of the air conditioner,
pump down the system following
the procedure
below so that refrigerant
is not released into the atmos-
phere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor
unit almost completely
so that it can be easily closed fully when the pressure gauge shows 0
MPa [Gauge] (0 Ibf/in. 2 [0 kgf/cm2]).
4) Start the emergency
COOL operation.
To start the emergency
operation
in COOL mode, disconnect
the power supply plug and/or turn off the breaker. After 15 seconds,
connect the power
supply plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency
COOL operation can be performed
continuously
for up to 30
minutes.)
5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 Ibf/in 2 [0.5 to 0
kgf/cm2]).
6) Stop the emergency
COOL operation.
To stop operation,
press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions
for details.
When pumping
down the refrigerant,
stop the compressor
before disconnecting
the refrigerant
pipes. The compressor
may burst
if air etc. get into it.
F