3
Start-up instructions
RISK OF LIFE
Due to fire or explosion.
Never use excessive force, when ad-
WARNING!
justing the gas control knob
(
Fig. 5).
Adjust the gas control knob only by
hand.
Never use a tool for adjusting the gas
control knob.
If you can not turn the gas control knob
by hand, do NOT try to repair it.
Contact a qualified service organizati-
on at this point.
5. Turn the gas control knob clockwise in the "OFF"
position. Do not use excessive force.
RISK OF LIFE
Due to ignition of flammable gases.
Wait 5 (five) minutes until all gas odors
WARNING!
have disappeared. Check to see if any
gas odors remain, also at floor level. In
case gas odors are still present, shut off
gas supply, shut electrical power to the
boiler and inform the service organiza-
tion or local gas utility company.
6. If you do not smell any gases, proceed to the next
step.
7. Open main gas supply.
USER NOTE
This unit is equipped with an pilot burner
that must be ignited manually. Follow the
instructions below to light the pilot burner.
8. Turn gas control knob (
PILOT position.
9. Push and hold the red pilot ignition button (
in.
8
Fig. 5) clockwise to the
Fig. 5)
3
2
1
Fig. 5
Gasarmatur GC124 SP
1 Gas control knob (shown in the "ON" position)
2 "PILOT" position
3 Red pilot ignition button
We reserve the right to make any changes due to technical modifications.