SIngle phaSe loaD
Always be sure to check the nameplate on the generator
and equipment to insure the wattage, amperage, frequency,
and voltage requirements are satisfactorily supplied by the
generator for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require
130—150% more wattage than the rating on the nameplate,
as the wattage is influenced by the efficiency, power factor
and starting system of the equipment.
NOTICE
If wattage is not given on the equipment's name plate,
approximate wattage may be determined by multiplying
nameplate voltage by the nameplate amperage.
WATTS = VOLTAGE x AmPERAGE
The power factor of this generator is 0.8. See Table 5 below
when connecting loads.
Table 5.
power Factor By load
type of load
Single-phase induction motors
Electric heaters, incandescent lamps
Fluorescent lamps, mercury lamps
Electronic devices, communication
equipment
common power tools
Table 6.
Cable Selection (60 hz, Single phase operation)
load in Watts
Current
in
At 100
At 200
Amperes
volts
volts
2.5
300
600
5
600
1200
7.5
900
1800
10
1200
2400
15
1800
3600
20
2400
4800
cAUTION: Equipment damage can result from low voltage
DCa150SSI/DCa150SSIu 60 hz gen. • operatIon anD partS manual — rev. #0 (11/23/09) — page 25
power Factor
0.4-0.75
1.0
0.4-0.9
1.0
0.8
maximum allowable Cable length
#10 Wire
#12 Wire
#14 Wire
1000 ft.
600 ft.
375 ft.
500 ft.
300 ft.
200 ft.
350 ft.
200 ft.
125 ft.
250 ft.
150 ft.
100 ft.
150 ft.
100 ft.
65 ft.
125 ft.
75 ft.
50 ft.
three phaSe loaD
When calculating the power requirements for 3-phase
power use the following equation:
NOTICE
If 3Ø load (kVA) is not given on the equipment
nameplate, approximate 3Ø load may be determined
by multiplying voltage by amperage by 1.732.
NOTICE
motors and motor-driven equipment draw much greater
current for starting than during operation.
An inadequate size connecting cable which cannot carry
the required load can cause a voltage drop which can
burn out the appliance or tool and overheat the cable. See
Table 6.
When connecting a resistance load such as an
incandescent lamp or electric heater, a capacity of up to
the generating set's rated output (kW) can be used.
When connecting a fluorescent or mercury lamp, a
capacity of up to the generating set's rated output (kW)
multiplied by 0.6 can be used.
When connecting an electric drill or other power tools,
pay close attention to the required starting current
capacity.
When connecting ordinary power tools, a capacity of up to
the generating set's rated output (kW) multiplied by 0.8 can
be used.
#16 Wire
DANGER
250 ft.
125 ft.
Before connecting this generator to any building's
electrical system, a licensed electrician must install
100 ft.
an isolation (transfer) switch. Serious damage to
the building's electrical system may occur without this
transfer switch.

LOAD APPLICATION