MULTIQUIP WHISPERWATT DCA10SPX4 Operation And Parts Manual page 22

Whisperwatt series 50 hz generators (kubota d1503-m diesel engine)
Table of Contents

Advertisement

DCA-10SPX4 /U4 — OUTPUT TERMINAL PANEL FAMILIARIZATION
100 VAC GFCI Receptacle
This100 VAC, 20 amp GFCI (Duplex Nema 5-20R)
receptacle can be used anytime the generator is in operation.
The receptacle is protected by a 20 amp circuit breaker.
The breaker can be located on the generator control panel.
Pressing the reset button resets the GFCI receptacle after
being tripped. Pressing the Test Button (See Figure 6) in
the center of the receptacle will check the GFCI function.
This receptacle should be tested at least once a month.
Figure 6. G.F.C.I. Receptacle
Twist Lock Dual Voltage 100/200 VAC Receptacle (Option)
There is one CS-6369 100/200V, 45 amp auxilliary twist-
lock receptacle (Figure 7) provided on the output terminal
panel. This receptacle is protected by a 45 amp circuit
breaker.
Figure 7. CS6369 Twist-Lock
Auxiliary Receptacle
PAGE 22 — DCA10SPX4/DCA10SPXU4 — OPERATION AND PARTS MANUAL — REV. #0 (08/05/09)
L5-30R Twist Lock 100 VAC Receptacle (Option)
There is one L5-30R, 100 VAC 30 amp auxilliary twist-lock
receptacle (Figure 8) provided on the output terminal panel.
This receptacle is protected by a 30 amp circuit breaker.
Figure 8. L5-30R Twist-Lock
Auxiliary Receptacle
L6-30R Twist Lock 200 VAC Receptacle (Option)
There is one L6-30R, 200 VAC 30 amp auxilliary twist-lock
receptacle (Figure 9) provided on the output terminal panel.
This receptacle is protected by a 30 amp circuit breaker.
Figure 9. L6-30R Twist-Lock
Auxiliary Receptacle
Turn the voltage regulator control knob (Figure 10) on
the control panel to obtain the desired voltage. Turning the
knob clockwise will increase the voltage, turning the knob
counter-clockwise will decrease the voltage.
Figure 10. Voltage Regulator Control Knob