Ac Receptacle Selection - Honda ES6500 Owner's Manual

Hide thumbs Also See for ES6500:
Table of Contents

Advertisement

AC Receptacle
Selection
The generator
has two separate
main power.
reducing
circuits.
T$;c&
two crrcurts
supply
equal
power
to dr ferent
receptacles
P
When two or more receptacles
are used; prevent
overloading
by
dividing
the load between
the two
ower circuits.
connected
to each receptacle
to balance the generator
load.
The total rated ampere draw is 41.7A.
'The
table
shows
the specifications
when
the 120/24OV locking
plug receptacle
is used for 120V.
Example:
Receptacle
3 has a 10A load connected
to it. Receptacle
4 has a
15A load connected
to it. Both receptacles
are powered
by main
power circuit
II. The equation
tells us that the total power draw on
circuit
II is 25A. This is a substantial
overload
of this circuit.
To
eliminate
the excess
power
draw
on circuit
II, the load
from
receptacle
3 should
be switched
to receptacle
2. Now circuit
I is
powering
the 10A load (less than 20.8A) and circuit
II is powering
a 15A load (less than 20.8A).
I 120V20A
8
2 120V 20A
3 120V20A
4 120V20A
8
5
120V20A
@&@
l20/24OV 30A