Parameters - Baxi Bioflo Installation & Servicing Instructions Manual

Pellet central heating system boiler
Table of Contents

Advertisement

For the Service Technician

4.5.1 Parameters

The following parameters can be selected with the arrow buttons, then confirmed using the Choose button.
– Number of burner starts
– Fuel quantity auger conveyor
– Delivery time ignition phase
– Hysteresis Burner ON
– Maximum value of set temperature
– Set temperature ext. heating requirement
– Profile ash removal
– Correction of cleaning interval
– Air intake/exhaust flap
– Limits for blower speed
– Install display module
– Language
– Installation
Number of burner starts
The number of burner starts of the BAXI Bioflo is displayed – Fig. 37.
Fuel quantity auger conveyor
The calculated fuel quantity (actual value) and the range is displayed in kg/h,
and can be adjusted – Fig. 38.
BAXI Bioflo
Actual
Factory setting:
value
Setting range:
Factory setting:
Range
Setting range:
Correc-
Factory setting:
tion
Setting range:
Delivery time ignition phase
Fuel quantity in the ignition phase – Fig. 39.
BAXI Bioflo
Factory setting:
Setting range:
Hysteresis Burner ON
Switching hysteresis for burner control – Fig. 40
Factory setting:
Setting range:
0 – 20 K
6.0 kg/h
±2 kg of range
6.0 kg/h
6.0 – 8.0 kg/h
0
±5
120 s
100 – 150 s
5 K
27
Number of
burner starts
1.350
Fig. 37
Back
Fuel quantity
Auger conveyor
Actual value
6.0 kg
Range
6.0 kg
Correction
Choose
Back
Fig. 38
Delivery time
ignition phase
120
Save
Fig. 39
Yes
No
Hysteresis
Burner ON
5
Save
Fig. 40
Yes
No
0
s
+
K
+

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bioflo 12 kw pear

Table of Contents