Operation - Fluke 1625 User Manual

Earth/ground tester
Hide thumbs Also See for 1625:
Table of Contents

Advertisement

1625
Users Manual

Operation

Connect the adapter according to the diagram and the designations E, S and H
(C1, P1 and P2 for US-version) to the tester and to a current clamp.
1625
EARTH / GROUND TESTER
START
TEST
DISPLAY
MENU
Resistance
Earth/Ground Resistance 300k
RA
2
4
POLE
3
POLE
4
POLE
CHANGE
ITEM
3
POLE
OFF
SELECT
Use the test cable contained in the set to connect the second current clamp to
the socket. Ensure that connections are in the correct polarity. Turn the rotary
switch of the tester to position
Use only current transformers referred to in this manual.
Clamp both transformers around the ground conductor to be tested.
Try to have a distance > 10 cm between the clamps for optimal re-
sults.
68
H
H/C2
S
S/P2
AC
300 k
DC Low Resistance 3k
R
R
POLE
2
POLE
4
POLE
ES/P1
E
E /C1
R
D 3 pole.
E
Note
Note
Black
EI-162AC
Red
EI-162X
edw063.eps