Earth/ground tester
Hide thumbs Also See for 1625:
Table of Contents

Advertisement

If the parallel connection of resistors, R1...Rn is considerably lower than the
ground connection under test R
1
1
1
R
R
1
2
U
R
then
is a reasonable approximation.
X
I
The test voltage (U) is applied without disconnecting ground rod and/or the
direct electrical connection by means of a clamp-on current transformer and
the current detected by a second current transformer.
Voltage
U
Current
I
After synchronous rectification of current and voltage the tester displays R
Stakeless Earth/Ground Resistance Testing
:
X
R
1
X
R
n
R
R
X
1
Principle of Operation
R
R
2
R
n-1
n
edw062.eps
.