Fault Messages - Kohler 14/20RESA Operation

Residential/commercial generator sets controllers: rdc2, dc2
Hide thumbs Also See for 14/20RESA:
Table of Contents

Advertisement

Warning (W) or
Shutdown (SD) Condition
Fault Message
AC Sens Lost
W (1 sec.)
SD (3 sec.) *
Accy PwrOver
W
Warning
ATS Com Error
W
ATS PhaseRot
W
Aux Input
SD *
Batt Chg Flt
W
Battery Voltage
W
High
Battery Voltage
W
Low
Engine Oil
SD *
Pressure Low
EngineSpeed
SD *
High
EngineSpeed
SD *
Low
Exer Not Sch
W
* Engine cooldown runs before shutting down.
26
Section 2 Generator Set Operation
AC sensing lost. In Auto mode, generator output
AC sensing is lost. Starts 10 seconds after
crank disconnect.
Warning: after 1 second if no output detected
after crank disconnect.
Shutdown: after 3 seconds if voltage was
present and then lost.
Accessory Power Overload. An over current
fault (short circuit) on the accessory controller
power output.
ATS communication error. Warning is displayed
if ATS interface connection is lost.
See Section 2.5.3.
ATS phase rotation mismatch. Transfer switch
phase rotation does not match, ATS will not
transfer.
Auxiliary input. An optional customer-connected
input is closed. (Digital input from optional PIM.)
Battery charger fault. Input to PIM from an
external battery charger (not the built-in battery
charger).
Engine starting battery voltage rises above 16
VDC for more than 10 seconds. Inhibited during
the engine crank cycle.
Clears when the battery voltage returns to an
acceptable level.
Engine starting battery voltage falls below 12.5
VDC for more than 90 seconds when the engine
is not running. Not operative during the engine
crank cycle.
Clears when the battery voltage returns to an
acceptable level.
The LOP switch indicates low oil pressure for
more than 5 seconds. Function becomes active
30 seconds after crank disconnect (30 second
inhibit).
Note: The low oil pressure shutdown does not
protect against low oil level. Check the engine
oil level regularly as recommended in Section 5.
Engine speed exceeds 115% of the normal
running speed for more than 0.3 seconds.
Engine speed drops below 85% of the normal
running speed for more than 3 seconds.
Exercise not scheduled. No exercise is
scheduled on the controller.
Check
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Check communication wiring between
transfer switch interface board and
generator set.
Correct the ATS connection. Refer to
the ATS Installation manual, wiring
diagrams, and labels on the transfer
switch.
Check customer-supplied equipment.
Check external battery charger.
Check the battery rating and
condition.
Check the battery charger operation.
Check the battery rating and
condition.
Check the battery charger operation.
Charge or replace the battery.
Check for leaks in the lubrication
system.
Check the oil level and add oil if the
level is low.
Contact an authorized
distributor/dealer for service.
Reduce the load.
Contact an authorized
distributor/dealer for service.
See Section 3.6 or 4.5 for instructions
to set the exerciser.
TP-6804 12/11