Rated Output kVA
80
Batt. Capacity Required
75 kWB
at Full Load Output
Number of Cells
AC OUTPUT
Configuration
Voltage
Voltage Regulation
Voltage Adj. Range
Voltage Unbalance
THD (V
)
OUT
Crest Factor
Transient Response
Transient Recovery Time
Frequency
Frequency Synch. Range
Frequency Slew Rate
Frequency Regulation
Phase Displacement
Output Current
96 A
Power Factor
0.9 (0.9 Lagging to 0.95 Leading within output kW rating)
Overload Capacity
Withstand Rating
ENVIRONMENTAL
Cooling
Operating Temperature
Relative Humidity
Altitude
Location
Paint Color
Clearance Required
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if no sidecars used.
G9000 Installation and Operation Manual
100
160
94 kWB
149 kWB
±1% (0 – 100% balanced load); ±2% (0 – 100% unbalanced load)
± 5.0% (in 0.5 V increments)
2% maximum at 100% unbalanced load
< 2% THD at 100% linear load; < 5% THD at 100% nonlinear load
±2% maximum at 100% load step; ±1% maximum at loss/return of AC power;
±5% maximum at load transfer to/from static bypass
±1% to ± 5% (selectable in 1% increments)
1 Hz/s to 5 Hz/s (selectable in 1 Hz/s increments)
±0.01% in free running mode
±1° @ 100% Balanced Load, ±3° @ 100% Unbalanced Load
120 A
192 A
125% for 2 minutes; 150% for 60 seconds
65,000 A (with optional fuses)
32 °F to 104 °F (0 °C to 40 °C). Recommended : 68゚F to 86゚F ( 20 °C to 30 °C)
5% – 95% Non Condensing
0 to 7380 feet No Derating at 40゚C
Indoor (free from corrosive gases and dust)
Top: 20 in. (508 mm)
Front: 40 in. (1016 mm)
Rear: 0 in. (0 mm)
225
300
210 kWB
311 kWB
240
3 phase, 3 wire
480 V
2.3
Less than 20ms
60 Hz
271 A
361 A
125% for 10 minutes; 150% for 60 seconds
100,000 A (with optional fuses)
Forced Air
Munsell N1.5 (Black)
Top: 23.6 in. (600 mm)
Front: 42.3 in. (1075 mm)
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if
500
750
518 kWB
776 kWB
601 A
902 A
Unity
Rear: 0 in. (0 mm)
23