The boiler must be mounted on a flat, vertical wall sur-
face which is large enough for the boiler including the
required minimum space requirement and the space
required for assembly (Fig. 4.3). These are shown on the
mounting template supplied with the boiler, and are:
– 5 mm on each side of the boiler,
– 145 mm underneath the boiler,
– 165 mm* above the boiler if using a flue pipe of
100 mm outside diameter,
– 246 mm* above the boiler if using a flue pipe of
125 mm outside diameter,
– 500 mm** in front of the boiler.
i
If the boiler is to be installed in a timber
framed building, it should be fitted in accord-
ance with "IGE/UP/7 Edition 2 Gas installa-
tions in timber framed and light steel framed
buildings".
It is not necessary to maintain a clearance between the
appliance and combustible materials or components,
since, at the rated heating power of the appliance, the
temperature here is always lower than the permitted
temperature of 85 °C.
4.5
Mounting the appliance
240
75
75
50
50
85
1
3
Fig. 4.4 Mounting the appliance
> Fix the hanging bracket (1) to the wall using the plugs
and screws (2) provided with the appliance.
> Hang the top of the appliance (3) onto the hanging
bracket using the suspension bracket.
Installation and maintenance instructions ecoTEC exclusive 0020017768_07
2
23
4.6
Removing the front case
Fig. 4.5 Removing the front case
To disassemble the front housing of the appliance, pro-
ceed as follows:
> Release the screw (1) on the bottom of the appliance.
> Push both the clamps (2) on the bottom of the appli-
ance together so that the front cladding releases.
> Pull the housing forwards at the lower edge and
remove the front cladding upwards.
Assembly
2
1
4
15