Checking The Connection Pressure (Gas Inlet Working Pressure); Checking Co Content And Adjusting If Necessary; Test Operation - Vaillant ecoTEC exclusive 832 Installation And Maintenance Instructions Manual

Table of Contents

Advertisement

8
Inspection and maintenance
8.8
Checking the connection pressure
(gas inlet working pressure)
To check the connection pressure proceed as described
in Section 6.2.3.
8.8.1
Checking CO
content and adjusting if
2
necessary
To check the air figure proceed as described in
Section 8.1.3.
8.9

Test operation

Always perform the following checks after completing
any inspection/maintenance task:
> Commission the appliance in accordance with the
instructions in the relevant operating manual.
Fig. 8.10 Function check
> Check the appliance for gas and water leaks.
> Check the flue system for leaks and that it is fixed
properly.
> Check over-ignition and that the flame on the burner
is burning evenly.
> Check the function of the heating (see Section 6.3.1)
and the hot water preparation (see Section 6.3.2)
> Document the inspection/maintenance tasks per-
formed in the form provided in the inspection or
maintenance contract.