Maintenance; Diagnostics - Trane FC Installation & Operation Manual

Unitrane fan-coil & force flo air conditioners 200 to 1,200 cfm, “zo” and later design sequence & “so” and later design sequence
Table of Contents

Advertisement

Diagnostics

Table
. Tracer ZN520 Diagnostics
M-D-1
Diagnostic
Fan
Condensate overflow
Off
Low temperature detection
Off
Low air flow - fan failure
Off
Space temperature failure
Off
Entering water temp failure
On
Discharge air temp low limit
Off
Discharge air temp failure
Off
Fresh air temp failure
On
Relative humidity failure
On
Generic 4-20ma failure
On
CO
Input failure
On
2
Maintenance required
On
Local fan mode failure
On
Local setpoint failure
On
Invalid unit configuration
Off
Normal – power up
On
Note 1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.
Note 2: When the entering water temperature is required but not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The
controller automatically clears the diagnostic once a valid entering water temperature value is present (non-latching diagnostic). When the entering water
temperature sensor fails, the controller prohibits all hydronic cooling operation, but allows the delivery of heat when heating is required. In the Cool mode, all cooling
is locked-out, but normal fan and outdoor air damper operation is permitted.
Note 3: When the outdoor air temperature sensor has failed or is not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition.
The controller automatically clears the diagnostic once a valid outdoor air temperature value is present (non-latching diagnostic). When the outdoor air temperature
sensor fails or is not present, the controller prohibits economizer operation.
60

Maintenance

Other Outputs (Note 1)
Valves Closed, Fresh air damper Closed, electric heat Off,
Baseboard heat Off
Valves Open, Fresh air damper Closed, electric heat Off,
Baseboard heat Off
Valves Closed, Fresh air damper Closed, electric heat Off,
Baseboard heat Off
Valves Closed, Fresh air damper Closed, electric heat Off,
Baseboard heat Off
Valves Enabled (Note 2), Fresh air damper Enabled (Note 2),
electric heat Enabled (Note 2), Baseboard heat Off
Valves Open, Fresh air damper Closed, electric heat Off,
Baseboard heat Off
Valves Closed, Fresh air damper Closed, electric heat Off,
Baseboard heat Off,
Valves Enabled, Fresh air damper Minimum position
heat Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, electric heat
Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, electric heat
Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, electric heat
Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, electric heat
Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, Electric Heat
Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, electric heat
Enabled, Baseboard heat Enabled
Valves Disabled, Fresh air damper Disabled, electric heat
Disabled, Baseboard heat Disabled
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled
diagnostics
3
, electric
UNT-SVX07A-EN