Viessmann VITOCROSSAL 200 Service Instructions Manual page 49

Type ct2, gas fired condensing boiler with matrix cylinder burner for natural gas e and ll
Hide thumbs Also See for VITOCROSSAL 200:
Table of Contents

Advertisement

Burner control unit flow diagram
After the controller issues a heat
demand, the following program
sequence will be run:
Phase
00
Fault
01
Waiting for heat demand
03
Fan idle state
04
Air pressure switch idle state
06
Fan ramp-up
07
Waiting for air pressure
08
VPS decision: Valve tightness check
09
VPS: Clear intermediate valve space
10
VPS test time: Valve 1
11
VPS: Fill intermediate valve space
12
VPS detection: Gas pressure
13
VPS test time: Valve 2
14
Pre-purge time
16
Ignition setting
17
Gas detection: Gas pressure limiter min.
18
Pre-ignition time
19
Ignition safety time (SZA)
20
SZA flame recognition
21
Flame stabilising time
23
Changing to control mode
24
Regulated operation
25
Changing to controlled shutdown
32
Afterburn time
33
Post-purge time
34
Restart blocking time
01
Waiting for heat demand
For shutdown:
35
Gas shortage: Gas pressure limiter min.
36
Maintenance program
Gas burner control unit flow chart
(cont.)
Duration
0 ...
0 ...
max. 2 min
max. 5 s
max. 2 min
max. 5 s
0.1 s
1 to 3 s
1 to 240 s
1 to 3 s
0.1 s
1 to 240 s
0 to 1 h
max. 2 min
0 ...
0 to 1 min
0.5 to 9.4 s
0.5 s
1 to 200 s
max. 2 min
0 ...
1 to 30 s
1 to 60 s
0 to 1 h
0 to 1 h
0 ...
0 ...
0 ...
49