Troubleshooting Diagnosis - Viessmann VITOCROSSAL 200 Service Instructions Manual

Type ct2, gas fired condensing boiler with matrix cylinder burner for natural gas e and ll
Hide thumbs Also See for VITOCROSSAL 200:
Table of Contents

Advertisement

Troubleshooting
Diagnosis
Faults with indication on the display and programming unit
(fault codes)
Message codes
Message
System character-
code
istics
A
Burner OFF
A
Burner OFF
C
Burner OFF
New parameter
memory stick
F
Burner is in a fault
state
F2 (flash-
Burner OFF
ing)
General process error
Fault code System character-
istics
F AA
Fan pressure is pro-
duced during the air
pressure switch idle
state check
F AA
The air pressure
switch contact is not
in the idle state
F AB
Air pressure switch
shows no air pres-
sure, fan does not
operate
F AB
Air pressure switch
shuts down during
operation
40
Cause
Measures
Gas pressure lim-
Check the gas pressure
iter fault
limiter
Lack of gas
Notify your gas supply
company
Data transfer from
Enter password (hexa-
the new para-
decimal number be-
meter memory
tween 0 and 255 or 00
stick with a pass-
and FF)
word
See fault code
See fault code steps
Connected dis-
Use current display
play is invalid
Cause
Measures
Wind influence on
Check the flue gas
fan
draught (chimney)
Air pressure
Replace the air pressure
switch faulty
switch
Air pressure
Replace air pressure
switch is faulty,
switch, connect or set
connected or set
correctly
incorrectly
Flue gas back
Remove flue gas back
pressure, con-
pressure, check for con-
densate banked
densate banked up, and
up
reset the burner control
unit