Expansion Vessel And System Pressure Check - Viessmann VITOCROSSAL 200 Service Instructions Manual

Type ct2, gas fired condensing boiler with matrix cylinder burner for natural gas e and ll
Hide thumbs Also See for VITOCROSSAL 200:
Table of Contents

Advertisement

Further details regarding the individual steps
Total hardness
Feedwater
Boiler
water
The pH value should be between 8.2 and 9.5.

Expansion vessel and system pressure check

Note
Please observe expansion vessel
manufacturer's instructions.
Carry out this test on a cold system.
1. Drain the system until the pressure
gauge indicates "0" or close the
cap valve on the expansion vessel
and reduce the pressure in the
expansion vessel.
Commissioning, inspection, maintenance
pH value
Water treatment
Boiler
Medium
water
2. If the pre-charge pressure of the
expansion vessel is lower than the
static system pressure, top up with
nitrogen until the pre-charge pres-
sure is raised by 0.1 to 0.2 bar.
3. Top up your heating system with
water until the filling pressure of
the cooled system is 0.1 to 0.2 bar
higher than the pre-charge pres-
sure of the expansion vessel.
Permiss. operating pressure: 5.5
bar
(cont.)