Commissioning, inspection, maintenance
Further details regarding the individual steps

Checking the gas type

1. Determine the gas type and Wobbe
index (Wo) from your gas supplier.
&
With the natural gas E setting,
the boiler can be operated in the
Wobbe index range 12.0 to 16.1
3
kWh/m
(43.2 to 58.0 MJ/m
&
With the natural gas LL setting,
the boiler can be operated in the
Wobbe index range 10.0 to 13.1
3
kWh/m
(36.0 to 47.2 MJ/m

Conversion to natural gas LL

(not in a and c)
1. Close the gas shut-off valve.
2. Switch OFF the control unit ON/
OFF switch.
3. Switch OFF the main isolator (out-
side the installation room) or the
power supply and prevent
unauthorised reconnection.
4. Pull cables from gas train.
10
2. In the delivered condition, the burn-
er is set up for natural gas E. If
required, convert the burner in
accordance with details provided
by your gas supply utility to a differ-
3
).
ent gas type (see page 10).
3. Record the gas type in the service
report (on page 61).
3
).
5. Undo fitting A.
6. Pull compensation hose G from
gas train.
(cont.)