Viessmann VITOCROSSAL 200 Service Instructions Manual page 41

Type ct2, gas fired condensing boiler with matrix cylinder burner for natural gas e and ll
Hide thumbs Also See for VITOCROSSAL 200:
Table of Contents

Advertisement

Diagnosis
(cont.)
Fault code System character-
istics
F AB
Fan does not run
F AD
The gas pressure
limiter signals no
gas pressure during
the safety time
F AE
Burner control unit
in fault state
F AF
Burner control unit
in fault state
F A0 and
Status duration too
F A1
long, fan ramp up
F A2
Burner control unit
in fault state
F A3
No password en-
tered for parameter
memory stick
F A4 and
Burner control unit
F A5
in fault state
F A6
The ionisation flame
monitor reports ex-
ternal light ingress
during the start or
after the post-purge
F A6
The ionisation flame
monitor reports ex-
ternal light ingress
during the start or
after the post-purge
Cause
Measures
Fan faulty; cables
Check cables and re-
are faulty or bro-
place the fan if required
ken
Gas shut-off valve
Open the gas shut-off
closed, gas pres-
valve and check the gas
sure limiter faulty
supply pressure; clean
the gas filter if required
Valve 1 leaking
Replace the gas train
Valve 2 leaking
Replace the gas train
Internal fault; fan
Replace the burner con-
cannot reach its
trol unit or fan
set value
Interruption -
Check the safety chain
(strapping plug fJ)
safety chain has
been opened
(strapping plug
fJ)
Values in burner
Enter password
control unit and
parameter mem-
ory stick are dif-
ferent; timeout
because pass-
word not entered
Internal error in
Replace burner control
feedback from
unit
gas safety valves;
output relay does
not respond
Ignition cables
Remove the short circuit
shorted out
Ionisation cable
Remove the short circuit
or electrode short
circuit
Troubleshooting
41