DHW cylinders
(cont.)
500 litre capacity
WW
Z
R
HV/SPR
HR
476
498
Inspection and cleaning aperture
E
Drain
HR
Heating water return
HV
Heating water flow
KW
Cold water
R
Additional cleaning aperture or immersion heaters
Cylinder capacity
a
b
d
Performance factor N
L
To DIN 4708.
Cylinder storage temperature T
= cold water inlet temperature +
cyl
+5 K/-0 K
50 K
Cylinder capacity
Performance factor N
at a heating water flow temperature of
L
90 °C
80 °C
70 °C
Performance factor N
L
The performance factor N
varies according to the cylinder storage
L
temperature T
.
cyl
Standard values for
→ 1.0 × N
■ T
= 60 °C
cyl
L
→ 0.75 × N
■ T
= 55 °C
cyl
L
→ 0.55 × N
■ T
= 50 °C
cyl
L
→ 0.3 × N
■ T
= 45 °C
cyl
L
Peak output (over 10 minutes)
Relative to the performance factor N
DHW heating from 10 to 45 °C.
Cylinder capacity
Peak output (l/10 min) at heating water flow temperature
90 °C
80 °C
70 °C
VITOSOL
KW/E
l
500
mm
923
mm
974
mm
1740
.
L
SPR
914
b
SPR Cylinder temperature sensor of the cylinder temperature control
or the control thermostat
(Connector R 1" with fem. reducer to R ½" for sensor well)
WW DHW
Z
DHW circulation
l
200
6.8
6.0
3.1
l
200
340
319
233
10
300
500
13.0
21.5
10.0
21.5
8.3
18.0
300
500
475
627
414
627
375
566