D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specified. Framing or finishing material closer than
the minimums listed must be constructed entirely of non-
combustible materials (i.e., steel studs, concrete board, etc).
Combustible Mantels
No mantels are allowed when using Studio-CE fronts.
Note: All dimensions are shown in millimeters
51
26
Figure 5.3 Minimum vertical and maximum horizontal
dimensions of combustibles above appliance
when using the DF-SOHOCE-BK dress guard.
22
305
279
254
229
203
178
356
330
152
305
127
279
102
76
254
229
203
178
152
127
OPENING OF FIREPLACE
Heat & Glo • SOHO-N-AUB • 2197-980 Rev. G • 2/13
381