Vp526 Three-Way High Pressure Water Valve - Honeywell Pneumatic Controls Engineering Manual

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

VP526 Three-Way High Pressure Water Valve

Dimensions in inches (millimeters)
CLEARANCE REQUIRED
TO SERVICE VALVE
1-1/2 (38)
1
MIN.
2-1/4 (57) DIA.
1-5/8
(41)
A
D
E
F
G
H
MINIMUM FOR
REMOVAL OF VALVE
COPPER
IN. (MM)
TUBING
VALVE
(O.D.)
A
B
C
SIZE
3/8
1/2
3-1/16
7/8
13/16
1-1/2
(78)
(22)
(20)
(38)
1/2
5/8
3-3/8
1-3/16
7/8
1-3/4
(85)
(30)
(22)
(44)
ALLOW 1-1/2 IN. (38 MM) MINIMUM CLEARANCE FOR REMOVING
1
ACTUATOR. ALLOW 2-1/2 IN. (63 MM) TO FACILITATE STRAIGHT ON
TUBING. IF CLEARANCE IS LESS THAN 2-1/2 IN. (63 MM), USE
AN ELBOW.
AIR CONNECTION
FOR 1/4 IN. (6 MM)
O.D. PLASTIC TUBING
B
C
D
E
F
G
H
3/8
1-1/2
3
5-3/4
(10)
(38)
(76)
(146)
7/16
1-11/16
3-7/16
6-1/4
(11)
(43)
(87)
(159)
M18807A
Three-way pneumatic mixing valve provides proportional control
of hot and/or cold water in unit air conditioners and fan coil
systems. Replacement devices are available for Johnson, Powers,
Robertshaw, Barber-Colman, and older Honeywell devices.
Small size permits installation where space is limited.
Direct-acting, rolling diaphragm actuator with integral high
temperature plastic air connector for 1/4 in. (6-mm) O.D. plastic
tubing.
Spring loaded, self-adjusting Buna-N "V"-ring packing replaceable.
Brass seats (integral lower, removable upper) and contoured plug
provide metal-to-metal seating.
Stainless steel stem.
Linear and constant total flow throughout full plug travel.
VP526 Typical Piping Diagram
CONTROL AIR
VP526A
SUPPLY
A
COIL
AB
B
Close-off Ratings for the VP526
PORTS
B
A
B
A
B
A
5
2
10
3
11
8
6
1
11
2
12
7
7
0
12
1
13
6
8
13
0
14
5
9
14
15
4
10
15
16
3
11
16
17
2
12
17
18
1
13
18
0
14
CLOSE OFF PRESSURE RATING, PSI (kPa)
(DIFFERENTIAL PRESSURE BETWEEN
SUPPLY AND RETURN LINES)
Valve Type: Unitary
Body Pattern: Three-way Mixing
Body Pressure: 250 psi (1724 kPa)
Air Connections: Push on for 1/4 in. O.D. plastic tubing
Valve Action: Proportional Normally Open Ports B to AB
Controlled Medium: Water
Type of End Connection: 45 deg. SAE flare
Operating Humidity Range (% RH): 5 to 95% RH
Temperature Range: 35 F to 250 F (2 C to 121 C)
Maximum Safe Actuator Diaphragm Temperature: 230 F (110 C)
Maximum Diaphragm Pressure: 29 psi (200 kPa)
70-6925
Valves
N. O. PORTS
B TO AB
RETURN
C2726
ALL C
s
V
0
10
20
30
40
50
60
70
(69)
(138)
(207)
(276)
(345)
(414)
(483)
C493-1