Vp525C Pneumatic Radiator Valve; Radiator - Honeywell Pneumatic Controls Engineering Manual

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

VP525C Pneumatic Radiator Valve

Dimensions in inches (millimeters)
1-1/2
(38)
1
2-1/4 DIAMETER (57)
A
B
E
C
D
1
1-1/2 in. (38 mm) MINIMUM CLEARANCE TO REMOVE
ACTUATOR. 2 1/2 in. (63 mm) MINIMUM CLEARANCE
TO FACILITATE STRAIGHT ON TUBING CONNECTION.
IF CLEARANCE IS LESS THAN 2 1/2 in. (63 mm)
USE AN ELBOW.
M16449A
Close-off Ratings at various Control Air Pressures
ACTUATOR
VP525C CLOSE-OFF
SPRING RANGE
AT MAXIMUM SYSTEM PRESSURE
PSI (kPa)
9
14
(62)
(97)
11
16
(76)
(110)
13
18
(90)
(124)
15
20
(103)
(138)
17
22
(117)
(152)
24
19
(131)
(165)
26
21
(179)
(145)
23
28
(159)
(193)
25
30
0
20
40
60
(172)
(207)
(0)
(138)
(276)
(414)
CLOSE OFF DIFFERENTIAL
PRESSURE RATINGS PSI (kPa)
AIR CONNECTION
FOR1/4 IN. (6 mm)
O.D. PLASTIC TUBING
COVER FASTENER
BODY STYLE
SIZE NPT
STRAIGHT THRU –
MALE UNION OUTLET
ANGLE – MALE
UNION OUTLET
80
100
120
140
(552)
(689)
(827)
(965)
C7714A
Normally-open, single-seated pneumatic radiator valve with
straight through or angle body construction provides proportional
control of two-pipe, hot water or steam systems. Replacement
devices are available for Johnson, Powers, Robertshaw, Barber-
Colman, and older Honeywell devices.
Available in several capacities and spring ranges for various
application requirements.
Easily replaceable actuator assembly for convenience of service.
Compact size for installation where space is limited.
Can be repacked without shutting down system.
1-1/2
(38)
1
2-1/4 DIAMETER (57)
A
B
D
C
A
B
C
3-1/2
(90)
2-1/2
(63)
1/2
1-3/8
(35)
(76)
3/4
3-1/2
(90)
1-3/8
(35)
3
3-1/4
(83)
2-5/8
(66)
1/2
1
(25)
(76)
3/4
3-1/8
(80)
1
(25)
3
VP525C Typical Piping Diagram
THERMOSTAT
BRANCHLINE
SYSTEM
SUPPLY
Valve Type: Unitary
Body Pattern: Two-way
Body Pressure: 150 psi (1034 kPa)
Air Connections: Push on for 1/4 in. O.D. plastic tubing
Valve Action: Proportional Normally Open
Controlled Medium: Water; Steam
Operating Humidity Range (% RH): 5 to 95% RH
Temperature Range: 40 F to 240 F (4 C to 116 C)
Maximum Safe Actuator Diaphragm Temperature: 230 F (110 C)
Maximum Diaphragm Pressure: 30 psi (205 kPa)
Accessories:
14004932-001 Pneumatic Valve Adapter (M6410/M7410 linkage and a
green main spring to allow to retrofit an electric actuator)
70-6925
Valves
AIR CONNECTION
FOR1/4 IN. (6 mm)
O.D. PLASTIC TUBING
COVER FASTENER
D
E
3/4
(19)
1-3/8
(35)
(29)
1-5/8
(41)
1-1/8
1-1/8
(29)
1-1/4
(32)
N.O.
C4654
101

Hide quick links:

Advertisement

Table of Contents
loading