Pressure Controllers
PP905 Static Pressure Sensor
Dimensions in inches (millimeters)
8-3/8 (212)
4-3/16
(107)
1 (25)
9 (229)
7-7/8 (200)
3/64
(1)
5/8
(16)
Application Type: Static Pressure
Airflow Usage: 0.021 cfm (9.9 ml/s)
Connections: Push-on barb for 1/4 in (6 mm) Diameter tubing
Mainline Air Pressure (min.): 16 psi (112 kPa)
Mainline Air Pressure (max.): 25 psi (175 kPa)
Maximum Safe Static Pressure: 28 in. wc (7 kPa)
Maximum Safe Operating Pressure:
Product Number
Action
PP905B1008
Can be set for Direct
Acting or Reverse Acting
42
customer.honeywell.com
2-1/2
KEYHOLE SLOTS
(63)
FOR FOUR (4) NO.
10 SCREWS
2-1/4
(57)
ALLOW 2-1/2 (63)
MINIMUM CLEARANCE
FOR COVER REMOVAL
X
4-1/8
(105)
M27075
25 psi (172 kPa)
Output Pressure
Range
(psi)
(kPa)
3 psi to
21 kPa to
15 psi
103 kPa
One-pipe, direct-or reverse-acting pressure sensor used with
RP908/RP920 Controllers to provide control of duct static,
velocity, or differential pressure in airflow applications.
Replacement devices available for Johnson, Powers, Robertshaw,
Barber-Colman, and older Honeywell devices.
•
Three-diaphragm design minimizes calibration shift with static
pressure changes in velocity pressure applications.
•
Not sensitive to normal supply air variations.
•
Continuous static, total, velocity, or differential pressure indication
available by using differential pressure gage.
PP905 in Pneumatic Static Pressure Application
NORMALLY
OPEN
DAMPER
PNEUMATIC
AUCTATOR
2
Pressure Range: 2 in. wc (0.5 kPa)
Mounting: Duct mount
Temperature Range: 40 F to 120 F (4 C to 50 C)
Accessories:
14004238-001 Static Pressure Duct Head for 1/4 in., 6 mm diameter
Plastic Tubing
Setpoint Range
(in. wc)
(kPa)
0 in. wc. to 7 in.
0 kPa to 1.7 kPa
wc. (Adjustable)
(Adjustable)
70-6925
DISCHARGE
DUCT
AIR
STATIC
REFERENCE
A
PP905B
C
SENSOR
3
9
RP920C
1
CONTROLLER
M
Span (Non-
Adjustable)
(in. wc)
(kPa)
Comments
2 in. wc.
0.5 kPa The setpoint determines
the midpoint of the span.
M5570A