Honeywell Pneumatic Controls Engineering Manual page 75

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

P658E Dimensions in inches (millimeters)
1-3/4
(44)
3-5/16
(84)
19/64
(8)
P658F Dimensions in inches (millimeters)
3/4
(19)
2-3/4
(70)
7/16
(11)
THREADED BARB PROTECTOR
5/8–18 UNF-2A MALE THREAD
Product
Number
Mounting
P658A1013 Surface (includes
case)
P658B1012 Panel mount
P658E1001
Panel mount
P658E1167
Panel mount
P658F1000
Panel, through
double D hole secured
with hex nut
2-7/8
(73)
1-1/4
(32)
15/64
(6)
15/64
(6)
5/8
1-1/4
(16)
(32)
C7432
2-7/8
(73)
1-1/4
(32)
C7434
Differential
Pressure
Setpoint Range (Field
Range
Adjustable)
Electrical
Connections
(psi)
(kPa)
(psi)
Screw
2 psi
14 kPa 2 to 24 psi 14 to 165 kPa Make R-W on pressure rise to setpoint
terminals
Screw
2 psi
14 kPa 2 to 24 psi 14 to 165 kPa Make R-W on pressure rise to setpoint
terminals
1/4 in. quick-
1 psi
7 kPa
2 to 17 psi 14 to 117 kPa Make COM-NC on pressure fall to
connect male
terminals
1/4 in. quick-
1 psi
7 kPa
2 to 25 psi 14 to 172 kPa Make COM-NC on pressure fall to
connect male
terminals
1/4 in. quick-
1 psi
7 kPa
2 to 17 psi 14 to 117 kPa Make COM-NC on pressure fall to
connect male
terminals
P658 Typical Piping
CONTROLLER
BRANCH LINE
M5436
Air Connections: Barb fitting for 1/4 in. (6 mm) O.D. plastic tubing
Operating Humidity Range (% RH): 5 to 95% RH, 80 F (27C) max
wet bulb
Temperature Range: 40 F to 140 F (4 C to 66 C)
Maximum Safe Operating Pressure: 30 psi (207 kPa)
Switch Operation: Converts pneumatic signal to electrical switching
action (spdt)
Switch Type: Pneumatic/Electric Switch
Motor Load: 1 hp @ 125 Vac, 2 hp @ 250 or 277 Vac
Resistive Load: 25A @ 125, 250 or 480 Vac
Frequency: 60 Hz
Pilot Duty Ratings: 750 VA @ 125, 250 or 277 Vac
Approvals:
Underwriters Laboratories, Inc.
(kPa)
Switching Action
plus differential; Make R-B on pressure
fall to setpoint
plus differential; Make R-B on pressure
fall to setpoint
setpoint; Make COM-NO on pressure
rise to setpoint plus differential
setpoint; Make COM-NO on pressure
rise to setpoint plus differential
setpoint; Make COM-NO on pressure
rise to setpoint plus differential
70-6925
Switches
TO OTHER
CONTROLLED
DEVICES
B
TO CONTROL
W
SIDE OF FAN
MOTOR STARTER
R
Category SDYF
Calibration
Factory
Calibrated at
10 psi
Factory
Calibrated at
10 psi
No Factory
Calibration
No Factory
Calibration
No Factory
Calibration
67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents