Mp953E, F Pneumatic Coil Valve Actuators - Honeywell Pneumatic Controls Engineering Manual

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

Valve Actuator

MP953E, F Pneumatic Coil Valve Actuators

Dimensions in inches (millimeters)
4
MINIMUM
CLEARANCE
2
MP953E &
MP953F
3
MP953C &
MP953D
OPERATION SIZE
1
NOMINAL DIA.
5-1/8 (130)
5 INCH
7-1/8 INCH
7-1/8 (181)
8-1/4 (210)
8 INCH
13-1/2 (343)
13 INCH
Product Number Action
MP953E1285
Direct Acting
MP953E1301
Direct Acting
MP953E1319
Direct Acting
MP953E1327
Direct Acting
MP953E1368
Direct Acting
MP953E1376
Direct Acting
88
customer.honeywell.com
1
POSITIONER
ON MP953E AND
MP953F ONLY
2
3
4
9-1/4 (235)
4-5/8 (117)
4-3/8 (111)
10-1/2 (267)
5-5/8 (143)
4-3/8 (111)
11-1/8 (283)
6-1/2 (165)
5-3/8 (137)
18-1/8 (460)
10 (254)
7-11/16 (195)
M13903
Spring Range
Actuator
Force
(psi)
Medium
4 psi to 11 psi
Low
4 psi to 11 psi
Low
4 psi to 11 psi
Low
4 psi to 11 psi
Medium
4 psi to 11 psi
Medium
4 psi to 11 psi
Pneumatic actuators provide proportional control of steam or hot
or cold liquids in HVAC systems by operating V5011, V5013, and
VGF valve assemblies. Replacement devices are available for
older Honeywell actuators.
Rolling diaphragm for long life and low hysteresis.
Easily attached to valve.
Can be installed after piping valve.
Slide lock feature permits simple engagement to valve stem.
Direct- or reverse-action control.
Integral positive positioner relay provides positive positioning under
varying load conditions.
Typical Piping for MP953E,F Pneumatic Valve Actuator Wiring
M
B
M
M5445A
Actuator Type: Valve
Fail Safe Mode: Spring Return
Air Connections: Pilot: Barbed fitting for 5/32 in. O.D. plastic tubing
Main: Barbed fitting for 1/4 in. O.D. plastic tubing
Temperature Range:
Maximum Operating Pressure:
Humidity Range:
5 to 95% RH
Diameter
(kPa)
(in.)
28 kPa to 76 kPa
8 in.
28 kPa to 76 kPa
5 in.
28 kPa to 76 kPa
5 in.
28 kPa to 76 kPa
5 in.
28 kPa to 76 kPa
8 in.
28 kPa to 76 kPa
8 in.
70-6925
THERMOSTAT
POSITIONER
PILOT
MP953
DA
VALVE
0 F to 140 F (-18 C to +60 C)
25 psi (172 kPa)
Stroke
(inch)
(mm)
Includes
1 1/2 in.
38 mm
Positive Positioner with 5 psi
(35 kPa) range
3/4 in.
19 mm
Positive Positioner with 3 psi
range (21kPa)
Positive Positioner with 5 psi
3/4 in.
19 mm
range (35 kPa)
3/4 in.
19 mm
Positive Positioner with 10 psi
range (70 kPa)
3/4 in.
19 mm
311851-062 Stem Extension
Assembly and Positive
Positioner with 3 psi range
3/4 in.
19 mm
311851-062 Stem Extension
Assembly and Positive
Positioner with 5 psi range

Hide quick links: