8.4.4Number of indoor units – displays how many indoor units the outdoor unit is communicating with.

8.4.5 Opening degree of electronic expansion valve:

Actual opening degree value equals the display data divided 8

8.5 Protection

8.5.1 Three minutes delay at restart for compressor.
8.5.2 Temperature protection of compressor discharge.
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 216°F<T5< 239°F (102°C<T5<115°C), the frequency or the compressor will decrease to a lower level
every 2 minutes until it reaches F1.
---If T5>239°F(T5>115°C) for 10 seconds, the compressor will stop and restart till T5<194°F (T5<90°C).

8.5.3 Low voltage protection

Model
A-VMH18DC-1
A-VMH27TC-1
A-VMH36QC-1
Note: if the low voltage protection occurs and does not resume within 3min, it will keep the protection after
the machine is restarted.
Display
1
2
3
4
VOLTAGE
VOLLIMT1
VOLLIMT2
VOLLIMT3
VOLLIMT1
VOLLIMT2
VOLLIMT3
230
200
245
220
200
185
VMH SerieS
Quantity of indoor unit
1
2
3
4
VOLREL1
No limit
VOLFRE1
VOLREL2
VOLFRE2
VOLREL3
Off
VOLREL1
VOLREL2
120
260
210
120
265
240
120
210
195
22
Heat Controller, Inc.
VOLREL3
VOLFRE1
VOLFRE2
135
62
135
78
135
54
54
45
42