Heat Controller, Inc.
7. Installation Details
7.1 Wrench torque sheet for installation
Outside diameter
mm
Ф6.35
Ф9.52
Ф12.7
7.2 Connecting the cables
The power wiring should always follow NEC and local codes, with respect to the unit's, rating plate. See
installation manual for additional information. Main power connection is 208/230V/1PH~60HZ.
The communicating cable, which connects between the indoor and outdoor units must meet all NEC and
local codes, with respect to the unit's rating plate. We recommend using 14 AWG/4 conductor Stranded THHN
Ф Ф
6
V cable.
Pipe length and elevation
Unit
9K
3/8'' (Ф9.52)
12K/18K
1/2'' (Ф12.7)
Max. Total length for all rooms
NOTES:
Capacity test is based on standard length and maximum allowance length is based on reliability.
Oil trap should be installed per (3-5 meters)10-15ft.
Outdoor connections are ¼" (Ф6.35 mm) liquid and 3/8" (Ф9.52 mm) gas, therefore a reducer is
provided with all 12/18k indoor sections.
inch
1/4
3/8
1/2
Pipe size
Gas inch
Liquid inch
(mm)
(mm)
1/4'' (Ф6.35)
1/4'' (Ф6.35)
VMH SerieS
Torque
N
m
.
15(153kgf.cm)
25(255kgf.cm)
35(357kgf.cm)
Max.
Standard
length
Elevation
(m)
B (m)
(5)
(10)
16.5ft
33ft
Dual-zone
(m)
(30)100ft
11
10
Additional tightening torque
N
m
.
16(163kgf.cm)
26(265kgf.cm)
36(367kgf.cm)
Max.
Additional
Length
refrigerant
A (m)
(15)
50ft
0.2 oz/ft
Tri-zone
(m)
Quad-zone
(45)150ft
(60)200ft
Service Manual
(g/m)
(20)
(m)