WARNING:
Turn offelectrical power before servic-
ing controls. Severe electrical shock
may result unless power is turned off.
Unit must be installed in compliance
with the National Electrical Code (NEC)
and local codes.
ELECTRICAL CONNECTIONS
1.
ELECTRICAL
SERVICE
High Voltage
a.
Install a branch circuit disconnect
of ad-
equate size per N EC. Locate the disconnect
within sight of the unit.
b.
Extend leads through
power wiring hole
provided. Connect L1 and L2 directly to the
contactor. (See Figure 9).
c.
Ground the air conditioning
unit using the
green grounding
screw
provided
in the
control panel.
Low Voltage
a.
Route 24v control wires through the sealing
grommet near the power entrance.
b.
Connect the control wires to the leads in
the low voltage area. (See Figure 10).
2.
OVERCURRENT
PROTECTION
In general, the best fuse or breaker for any air
conditioner
is the smallest size that will permit
the equipment
to run under normal use and
service without nuisance trips. Such a device,
sized
properly,
gives
maximum
equipment
protection. The principal reason for specifying
a time delay type is to prevent nuisance trips
when the unit starts.
In the event that a fuse does blow or a breaker
trips, always determine the reason, Do not arbi-
trarily put in a larger fuse or breaker and do not,
in any case, exceed the maximum size listed on
the data label of the unit.
3.
LOCATING THE THERMOSTAT
Locate the thermostat
away from drafts and
slamming doors and place itwhere there is a free
flowof air. Mount on an inside wall approximately
five feet from the floor.
Do not locate near a lamp, kitchen range, direct
sunlight,
or in line with air flow from supply
registers.
These units are two stages Cooling and Heat-
ing units. They
require
a 2-stage
Cooling/
Heating thermostat. The heat-cool thermostat
is equipped with a system HEAT-COOL switch,
which provides a positive means of preventing
simultaneous
operation
of the heating
and
cooling units. The thermostat
is also equipped
with on ON-AUTO fan switch which allows the
home owner to operate the indoor blower when
air circulation
is desired.
Connect the low voltage wires to the respective
terminals on the thermostat base. See thermostat
instruction sheet for more detailed information.
(See Figure 10).
Refer to furnace
installation
instructions
for
required connections
and proper heat anticipa-
tor setting when installing unit with an external
furnace.
If two stage heating is desired, an optional
outdoor thermostat
may be installed: Connect
the thermostat to the orange low voltage wire and
the W terminal on the indoor thermostat
base
(See Figure 10). See the thermostat instructions
for details on setting the outdoor thermostat.
4.
ELECTRIC HEAT PACKAGE (OPTIONAL)
The air conditioner is shipped without an auxil-
iary electric heat kit installed. If electric heat is
desired, an accessory
Heater Kit must be field
installed. See Specifications
Sheet for available
kits and their applications.
Select the correct size heat package for the
installation.
Follow installation instructions provided with
each heater kit.
Installation
is most easily accomplished
before making duct or electrical
connec-
tions.
The blower must be set to high speed for
electric heat operation.