Installation
Instructions
(cont'd)
Venting (cont'd)
CUTTING
OPENING
THROUGH
AN OUTSIDE
WALL AND COLLAR INSTALLATION
After reading the manual and you have determined the location
of the opening in the wall, (using the drawing below), cut a 3½"
hole through an exterior wall.
NOTE: When determining location of the opening in the
outside wall allow for the ¼" rise per foot that has taken
place in the horizontal run.
CONNECTING
PVC, ABS OR CPVC PIPE VENT TC
BLOWER
1. The manufacturer
has supplied
a 3" PVC Schedule 40 street
elbow for connection
to the water heater when turning imme-
diately horizontally
off the blower.
Place the elbow in the
required
direction
on the blower
and using 3 sheet metal
screws, attach the elbow.
_
t
v
I I" MIN.
_
MIN. RISE¼"
PERFOOT
40 GAL.- 60"
50 GAL.- 59½"
I
I
The 3" PVC, ABS or CPVC Schedule 40 vent pipe can be run
from the water heater through the wall or from the wall to the
water heater, whichever
is most convenient.
The vent pipe must
extend a minimum
of 1½" through the exterior wall. Extending
the vent cap as far as possible from the surface of the exterior
wall will help minimize
discoloration
of the wall in this area
which may be caused by the flue gases. Note that the inside col-
lar must be slipped over the vent piping before locating the pipe
through
the wall. Before securing the inside and outside collars
to the wall, use a silicone sealer between
pipe and opening to
insure a water and air tight seal.
I
I
2. If there is to be a vertical run of vent from the blower, the 3"
PVC or ABS pipe must be attached to the blower using 3 sheet
metal screws. Additionally, you must seal all joints using a suit-
able silicone sealer such as GE RTV-103 or equivalent.
I
INSTALLATION SHOWING USE OF PVC, ABS OR
CPVC PIPE
/
....ImER,O, w _
- EXTS_IOI
WALL
CO
VENT CAP MUST BE
DOWNWARD
18