2.6
Shutoff Characteristic of the Customer's Distribution Panel
(Only When Connected to the Power Distribution Box)
To protect the device when it is connected to the customer's distribution panel through a power distribution box,
the breaker of the device (or the power distribution box) must trip before the corresponding breaker in the customer's
distribution panel. For this reason, the breakers in the customer's distribution panel must meet the characteristics
listed in
TABLE 2.8 Breaker characteristics for the customer's distribution
panel. Use only breakers that meet these
characteristics.

TABLE 2.8 Breaker characteristics for the customer's distribution panel

Power input
Device name
Breaker for use in countries other than
Breaker for use in
European countries (*)
Europe (*)
200 to 240 VAC
Power distribution box 30 A
32 A
* Capacity of a breaker in the customer's distribution panel
Use a long-time-delay type of breaker whose characteristics correspond to phase D shown in
FIGURE 2.20
Distribution panel breaker characteristics
(IEC898 or DIN0641 Part II). Alternatively, use a slower breaker.