Func.
Code
B_12/
Level of electronic thermal setting
B212
B_13/
Electronic thermal characteristic
B213
• 00 Reduced torque • 01 Const. torque
B_21
Overload restriction operation mode
• 00 Disabled
• 01 Enabled for accel and constant
speed
• 02 Enabled for constant speed only
B_22
Overload restriction setting
B_23
Deceleration rate at overload restriction
B_31
Software lock mode selection
• 00 Low-level access, [SFT] blocks
edits
• 01 Low-level access, [SFT] blocks
edits (except F_01 and Multi-speed
parameters)
• 02 No access to edits
• 03 No access to edits except F_01 and
Multi-speed parameters
B_81
[FM] terminal analog meter adjustment
B_82
Start frequency adjustment
B_83
Carrier frequency setting
B_84
Initialization mode (parameters or trip
history)
• 00 Trip history clear
• 01 Parameter initialization
B_85
Country code for initialization
• 00 Japan version
version
• 02 US version
B_86
Frequency scaling conversion factor
B_87
STOP key enable
• 00 Enable
B_88
Restart mode after FRS
• 00 Restart from 0Hz
• 01 Restart from frequency detected
from actual speed of motor
Name / Description
• 01 Europe
• 01 Disable
18
Default
Value
–FE / –FU /
–FR
Rated
current of
each inverter
01 / 01 / 00
01
Rated
current
x 1.25
1.0
01
80
0.5
5.0 / 5.0 /
12.0
00
01 / 02 / 00
1.0
00
00
Set
Value