is
Subject
Wall flue terminal set:
•
1x Wall flue terminal (incl. wall flange
& clamping ring)
•
1x Pipe 500 mm
•
1x Bend 90°
Pipe material
Pipe diameters
(1) No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
manufacturer or wholesaler.
Subject
Roof flue terminal set:
•
1x Wall flue terminal (incl. clamping
ring)
•
1x Pipe 1000 mm
•
1x Mounting flange
Pipe material
Pipe diameters
(1) No other roof flue terminal is permitted. Use this item number to order the roof conduit set from
supplier,manufacturer or wholesaler.
3.9.4
Instruction manual SGE
C13 Concentric wall flue terminal specifications
Art. No.
Construction
Manufacturer
Type
Construction
Chimney flue
Air supply
Chimney flue
Air supply
C33 concentric roof flue terminal specifications
Art. No.
Construction
Manufacturer
Type
Construction
Chimney flue
Air supply
Chimney flue
Air supply
Parallel connections
The table states the maximum pipe lengths for parallel systems. The maximum
pipe length depends on the chosen diameter.
Warning
Install flue component pipe runs with a run-off of 5 mm per metre.
Chimney flue requirements for parallel systems
1
Appliance
Diameter
SGE 40
SGE 60
100 mm
SGE 40
SGE 60
130 mm
1) Parallel systems with diameter of 130 mm or 150 mm. If the maximum total
length for a diameter of 130 mm is insufficient, 150 mm diameter must be
used. Any diameter enlargement must be carried out on both air supply and
chimney flue.
Description
1
0302 504
Concentric
Muelink & Grol
M2000 MDV SEC
Concentric
Thick-walled aluminium with lip ring seal
Thin-walled galvanised sheet steel
Ø 100 mm
Ø 150 mm
Description
1
0304 423
Concentric
Muelink & Grol
M2000 DDV HR-C
Concentric
Thick-walled aluminium with lip ring seal
Thin-walled galvanised sheet steel
Ø 100 mm
Ø 150 mm
Maximum
L
equivalent
total length
90° bend
25 m
4.6 m
100 m
2.4 m
L
equivalent
bend 45°
1.2 m
1.4 m
33