Type of appliance
B23
C13
C33
C43
C53
C63
3.9.3
Instruction manual SGE
Explanation of type of appliance
Description
Air for combustion is drawn from the boiler room.
Concentric and / or parallel wall flue terminal
Concentric and / or parallel roof flue terminal
Appliances on common air supply and flue gas discharge (concentric and / or
parallel) in multi-storey building.
Air supply and flue terminal types mixed.
Appliances supplied without flue components and / or terminal. These
appliances must be installed in compliance with local regulations.
Note
Make sure that the chimney discharges into an area where this is permitted
for this category of appliance.
Concentric connections
The table shows the requirements for concentric systems.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre.
Chimney flue requirements for concentric systems (C13, C33)
Appliance
Diameter
SGE 40
SGE 60
100/150 mm
Caution
Both conditions stated in the table must be fulfilled.
Even if there are less bends than the stated maximum, the maximum pipe
length may not be exceeded.
Even if the total pipe length is less than the stated maximum, the maximum
number of bends may not be exceeded.
Maximum length Maximum
number of 90°
bends
15 m
4
31