Omron WIRED REMOTE I-O System Manual page 86

Rack pcs
Table of Contents

Advertisement

Self-Diagnosis
Error Before Operation: C500 Masters and Slaves
Programming
LEDs on Master
Console LEDs
TR/
TEST
ERR
OK
CPU WAITING
flash
not lit
flash
not lit
lit
not lit
CPU WAITING
flash
not lit
/lit
or
REMOTE I/O
ERR
lit
not lit
REMOTE I/O
not
not lit
ERR
lit
or
VER ERR
I/O VER ERR
not
not lit
lit
LEDs on
Slave
END
LINE
TR/
ERR
RS
ERR
ERR
CHK
lit
not lit lit
not lit lit
not lit not lit
lit
not lit not lit
flash
not lit lit
not lit lit
not
lit
lit
not lit lit
lit
---
not lit lit
not lit lit
---
not lit lit
lit
not
not lit lit
not lit lit
lit
not
not lit lit
not lit lit
lit
Remote
Cause
Terminal LEDs
POWER TR/
ERR
lit
Terminator not set. Set farthest Unit
Transmission line
broken or wired
incorrectly.
Slave and Remote
Terminal points
exceed 512.
Power not
supplied to
terminator Slave.
not
Power not
lit
supplied to
terminator Remote
Terminal.
lit
Multiple
terminators set.
Refer to 7-7 Slave
Unit Numbers with
Multiple Termina-
tors.
lit
Transmission line
shorted.
lit
Same unit number
or word set twice
on Slaves.
lit
lit
Slave I/O bus
error.
lit
CPU Unit error in
Master.
lit
I/O table not
written or I/O table
inconsistency.
(LEDs will go out
after TR/ERR LED
on Master flashes
and terminator
LEDs are lit for
several seconds.)
Section 7-1
Correction
from Master as
terminator.
Correct
transmission line
Reduce total
number of points.
Supply power to
Slave.
Supply power to
Remote Terminal.
Set only one
terminator for
each Master.
Correct
transmission line.
Correct settings
so same word is
not allocated
twice.
Check Slave, I/O
Units on Slave,
and Slave's Rack.
Replace Master.
Check I/O table on
Programming
Console and
correct if
necessary. If I/O
table verifies,
check all Slaves
not set as
terminators.
77