Omron WIRED REMOTE I-O System Manual page 62

Rack pcs
Table of Contents

Advertisement

Masters and Slaves
Indicators
XMT/RCV
ERROR1
not lit
not lit
not lit
flash
not lit
not lit
---
lit
---
---
lit
lit
flash
flash
lit
flash
lit
lit
flash
lit
flash
C200H Slave Switches
Terminator Selector
DIP Switch
Pins 1 through 3: Unit Number
52
C200H Slaves indicators function together to show the status of the System.
The RUN indicator is controlled by the mode setting on the CPU Unit.
ERROR2
RUN
not lit
System not started or pow-
er off.
---
Normal transmission
not lit
Transmission error
not lit
I/O bus error
---
I/O verification error
not lit
I/O setting error
---
Expansion I/O Rack miss-
ing.
The DIP switch and terminator selectors are accessed by removing the
switch cover on the front of the Slave. Use a regular screwdriver to open the
cover if necessary. Always be sure that the PC and Slave power are turned
off before setting the switches.
Terminator Setting
Unit number*
0
1
2
3
4
5
6
7
*Unit numbers 0 and 1 can be set for C120 and C500 Systems; unit numbers
0 through 4 for C200H Systems; and 0 through 7 for C1000H and C2000H
Systems.
Status
Master is still testing System or power off.
Power has not yet been turned on.
Normal transmissions are occurring be-
tween Slave and Master.
Error has occurred in transmissions with
Master.
Error has occurred in I/O bus connecting
Slaves to I/O Units.
An I/O Unit configuration of Slave Rack
has changed.
An I/O Unit designation on the Slave Rack
is wrong.
An Expansion I/O Rack connected to the
Slave Rack with I/O Connecting Cable
cannot be confirmed by the PC.
Terminator
(Termination resistance ON)
Not terminator
(Termination resistance OFF)
Pin 1
2
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
Section 4-1
Meaning
3
OFF
ON
OFF
ON
OFF
ON
OFF
ON