Standard connections

3-phase 200 V AC
3-phase 400 V AC
To wire the control circuit power
supply and main circuit power
supply separately, be sure to
remove the J51 connector
wire first.
Frequency setting unit
500 to 2 kΩ

Terminal block specifications

Terminal
Main circuit power supply input
R/L1, S/L2, T/L3
Inverter output
U/T1, V/T2, W/T3
External DC reactor terminal
PD/+1, P/+
Braking resistor
P/+, RB
connection terminals
Regenerative braking
P/+, N/-
unit connection terminal
Grounding
10
DC reactor
(optional)
J51
Short-circuit
wire
Control circuit
power supply
Multi-function input 1
Multi-function input 2
Multi-function input 3
Multi-function input 4
Multi-function input 5
Multi-function input 6
Multi-function input 7
Multi-function input 8
Sequence input common
Thermistor
Frequency reference power supply
Frequency reference input (voltage)
Frequency reference auxiliary input (voltage)
Frequency reference input (current)
Frequency reference common
Name
PD/+1
P/+
N/-
R/L1
S/L2
T/L3
R
T
Ro
To
P24
CM1
FW
1
2
3
4
5
6
7
8
PLC
TH
H
O
Option 1
O2
OI
Option 1
L
Function (signal level)
Used to connect line power to the drive.
Used to connect the motor
Normally connected by the short-circuit bar. Remove the short-circuit bar between +1 and P/
+2 when a DC reactor is connected.
Connect option braking resistor (if a braking torque is required)
Connect optional regenerative braking units.
For grounding (grounding should conform to the local grounding code.)
Braking resistor
(optional)
RB
U/T1
V/T2
W/T3
AL1
Relay output *1
AL2
AL0
Common
11
Multi-function output 1
12
Multi-function output 2
13
Multi-function output 3
14
Multi-function output 4
15
Multi-function output 5
CM2
Multi-function output common
SP
SN
RS485 communication
RP
For termination
resistors
SN
Analog monitor output
AM
(voltage output)
Analog monitor output
AMI
(current output)
Digital monitor output
FM
(PWM output)
Frequency inverters
M

Advertisement

Table of Contents
loading

Table of Contents